Made of High-quality Silicon-steel Sheets, and Laminated by Steps
Low loss, Low noise, and High Short-circuit Withstand Capacity, Etc
Wildly Used in Power Station, Power Plant, and Gets High Praise from Them
Passed a Complete Set of National Tests and the Short-circuit Withstand Capacity Test.
The core of 110kV power transformers is made of high-quality silicon-steel sheets, and laminated by steps. It is advantageous in low loss, low noise, and high short-circuit withstand capacity, etC. Now it is wildly used in power station, power plant, and gets high praise from them. SZ11-63000/110 transformers have passed a complete set of National tests and the short-circuit withstand capacity test.
110kV Double -winding Power Transformers with On -load Tap -changer
| Rated Capacity | Voltage ratio (KV) |
Vector Group | No-load Loss | No-load Current | Full-load Loss | Impedance | ||
| (kVA) | HV | Tapping Range | LV | (kW) | (%) | (kW) | (%) | |
| 6300 | 110 121 |
±8×1.25% |
6.3 6.6 10.5 11 |
YNd11 | 10 | 0.6 | 36 | 10.5 |
| 8000 | 12 | 0.6 | 45 | |||||
| 10000 | 14.2 | 0.55 | 53 | |||||
| 12500 | 16.8 | 0.55 | 63 | |||||
| 16000 | 20.2 | 0.5 | 77 | |||||
| 20000 | 24 | 0.5 | 93 | |||||
| 25000 | 28.4 | 0.45 | 110 | |||||
| 31500 | 33.8 | 0.45 | 133 | |||||
| 40000 | 40.4 | 0.4 | 156 | |||||
| 50000 | 47.8 | 0.4 | 194 | |||||
| 63000 | 56.8 | 0.35 | 234 | |||||
| 75000 | 63.4 | 0.35 | 278 | |||||
| 90000 | 73.1 | 0.3 | 320 | |||||
| 120000 | 91.2 | 0.3 | 397 | |||||
110kV Three -winding Power Transformers with On -load Tap -changer
| Rated Capacity | Voltage ratio (KV) |
Vector Group | No-load Loss | No-load Current | Full-load Loss | Impedance | |||
| (kVA) | HV | Tapping Range | LV | (kW) | (%) | (kW) | Step -Down |
Step -Up |
|
| 6300 | 110 ±8× 1.25% |
35 37 38.5 ±2×2.5% or ±5% |
6.3 6.6 10.5 11 |
YNd110d11 | 12 | 0.6 | 47 | H-M 10.5 H-L 17-18 M-L 6.5 |
H-M 17-18 H-L 10.5 M-L 6.5 |
| 8000 | 14.4 | 0.6 | 56 | ||||||
| 10000 | 17.1 | 0.55 | 66 | ||||||
| 12500 | 20.2 | 0.55 | 78 | ||||||
| 16000 | 24.2 | 0.5 | 95 | ||||||
| 20000 | 28.6 | 0.5 | 112 | ||||||
| 25000 | 33.8 | 0.45 | 133 | ||||||
| 31500 | 40.2 | 0.45 | 157 | ||||||
| 40000 | 48.2 | 0.4 | 189 | ||||||
| 50000 | 56.9 | 0.4 | 225 | ||||||
| 63000 | 67.7 | 0.35 | 270 | ||||||
66kV Double-winding Power Transformers with Off -circuit Tap -changer
| Rated Capacity | Voltage ratio (KV) |
Vector Group | No-load Loss | No-load Current | Full-load Loss | Impedance | ||
| (kVA) | HV | Tapping Range | LV | (kW) | (%) | (kW) | (%) | |
| 6300 | 110 121 |
±2×2.5 | 6.3 6.6 10.5 11 |
YNd11 | 9.2 | 0.6 | 36.0 | 9 |
| 8000 | 11.2 | 0.6 | 42.7 | |||||
| 10000 | 13.2 | 0.55 | 50.4 | |||||
| 12500 | 15.6 | 0.55 | 59.8 | |||||
| 16000 | 18.8 | 0.5 | 73.5 | |||||
| 20000 | 22.0 | 0.5 | 89.1 | |||||
| 25000 | 26.0 | 0.45 | 105.3 | |||||
| 31500 | 30.8 | 0.45 | 126.9 | |||||
| 40000 | 36.8 | 0.4 | 148.9 | |||||
| 50000 | 44.0 | 0.4 | 184.5 | |||||
| 63000 | 52.0 | 0.35 | 222.3 | |||||
66kV Double-winding Power Transformers with On -load Tap -changer
| Rated Capacity | Voltage ratio (KV) |
Vector Group | No-load Loss | No-load Current | Full-load Loss | Impedance | ||
| (kVA) | HV | Tapping Range | LV | (kW) | (%) | (kW) | (%) | |
| 6300 | 63 66 69 |
±8×1.25% | 6.3 6.6 10.5 11 |
YNd11 | 10 | 0.6 | 36.0 | 9 |
| 8000 | 12 | 0.6 | 42.7 | |||||
| 10000 | 14.2 | 0.55 | 50.4 | |||||
| 12500 | 16.8 | 0.55 | 69.8 | |||||
| 16000 | 20.2 | 0.5 | 73.5 | |||||
| 20000 | 24 | 0.5 | 89.1 | |||||
| 25000 | 28.4 | 0.45 | 105.3 | |||||
| 31500 | 33.7 | 0.45 | 126.9 | |||||
| 40000 | 40.3 | 0.4 | 148.9 | |||||
| 50000 | 47.6 | 0.4 | 184.9 | |||||
| 63000 | 56.2 | 0.35 | 222.3 | |||||